ABB PST Series Installation And Commissioning Manual page 166

Table of Contents

Advertisement

&KDSWHU 
7URXEOH VKRRWLQJ
6WDWXV
37& SURWHFWLRQ
Power on
Fault
Protection
2TQV 26%
4GUGV
7K\ULVWRU RYHUORDG SURWHFWLRQ The softstarter is too small.
Power on
Fault
Protection
2TQV 5%4 1.
4GUGV
166
3RVVLEOH FDXVH
An over-temperature is detected
by the PTC thermistors in the
motor.
$CEM
Too many starts / hour.
The ramp time for start is too
long.
$CEM
6ROXWLRQ
• Check that the PTC circuit is closed and
that the inputs are connected.
• Check and correct the reason for the
overheating.
• Wait for the motor to cool sufficiently and
restart.
• Check and replace the softstarter with
one of a suitable size.
• Check and decrease number of starts /
hour.
• Check that current limit level is not set
too low.
• Check that the ramp time for start is not
too long.
1SFC132003M0201