ABB PST Series Installation And Commissioning Manual page 159

Table of Contents

Advertisement

6WDWXV
Motor humming / starts without
given start signal.
Bad motor sound during start
and operation.
Bad motor sound during stop.
Motor does not start when giving
start command using the hard-
ware inputs.
Motor does not start when giving
start command using the fieldbus
communication.
1SFC132003M0201
&KDSWHU  7URXEOH VKRRWLQJ
 *HQHUDO
This chapter is a guide that can be used in case problems
should arise with the softstarter or the application.
The softstarter normally indicates a fault with LED Fault,
and the LCD displays what type of fault it is. When a
protection is activated it will be indicated with LED
Protection and the LCD displays what type of protection is
active.
Faults not displayed in the softstarter can also be found in
this chapter.
 *HQHUDO SUREOHPV DQG IDXOWV
3RVVLEOH FDXVH
Shorted thyristor.
By-pass contactor stuck in
closed position.
Inside Delta connection wrong.
Wrong ramp time for stop.
Control wiring not correct.
Start and stop command given at
the same time.
Keypad is in Local Control menu.
Setting of fieldbus parameter
wrong.
6ROXWLRQ
• Check and replace.
• Check and correct the reason.
• Check and correct the wiring.
• Try different ramp times (some adjust-
ments can be necessary for best
result).
• Check connections for start and stop.
• Check that start and stop command is
not given at the same time.
• Check that the keypad is not in Local
Control menu.
• Check that parameter Fieldbus Ctrl is
set to No.
• Check that parameter Fieldbus Ctrl is
set to Yes.
• Check that bit "Enable" is used.
• Check that programmable inputs have
correct settings.
&KDSWHU 
7URXEOH VKRRWLQJ
159