ABB PST Series Installation And Commissioning Manual page 109

Table of Contents

Advertisement

1R 7\SH
1SFC132003M0201
 3DUDPHWHUV
3DUDPHWHU
1 Read/Write
Setting Ie
2 Read/Write
Start Ramp
3 Read/Write
Stop Ramp
4 Read/Write
Init Volt
5 Read/Write
End Volt
6 Read/Write
Step Down
7 Read/Write
Current Lim
8 Read/Write
Kick Start
9 Read/Write
Kick Level
10 Read/Write
Kick Time
11 Read/Write
Start Range
12 Read/Write
Stop Range
13 Read/Write
Overload
14 Read/Write
OL Class
15 Read/Write
OL Class S
16 Read/Write
OL Class R
17 Read/Write
OL Op
18 Read/Write
Locked Rotor
19 Read/Write
Lock R Lev
20 Read/Write
Lock R Time
21 Read/Write
Lock R Op
22 Read/Write
Underload
23 Read/Write
Underl Lev
24 Read/Write
Underl Time
25 Read/Write
Underl Op
26 Read/Write
Phase Imb
27 Read/Write
Ph Imb Lev
28 Read/Write
Ph Imb Op
29 Read/Write
High I
30 Read/Write
High I Op
31 Read/Write
Phase Rev
32 Read/Write
Ph Rev Op
33 Read/Write
PTC
)LHOGEXV FRPPXQLFDWLRQ RSWLRQ
'HVFULSWLRQ
Setting current
Time for start ramp
Time for stop ramp
Initial voltage for start ramp
End voltage for stop ramp
Voltage value to which the softstarter
shall step down at stop and where it
shall commence the stop ramp.
Level of the current limit.
Selection of Kick start
Level of Kick start if selected
Time for Kick start if selected
Selectable range for start ramp
Selectable range for stop ramp
Overload protection
Overload Class
Overload Class, Dual type, Start
Class
Overload Class, Dual type, Run
Class
Type of operation for overload pro-
tection
Locked rotor protection
Trip level for locked rotor protection
Trip time for locked rotor protection
Type of operation for locked rotor
protection
Underload protection
Trip level for Underload protection
Trip time for Underload protection
Type of operation for Underload pro-
tection
Phase imbalance protection
Trip level for phase imbalance pro-
tection
Type of operation for phase imbal-
ance protection
High current protection
Type of operation for high current
protection
Phase reversal protection
Type of operation for phase reversal
protection
PTC protection
&KDSWHU 
5DQJH
8QLW
0 – 3000 (*)
Amp
1 – 120
Sec
0 – 120
Sec
30 – 70
%
30 – 70
%
30 – 100
%
2,0 – 5,0
x Ie
No, Yes
50 – 100
%
0,1 – 1,5
Sec
1-30s, 1-120s
0-30s, 0-120s)
No, Normal, Dual
10A, 10, 20, 30
10A, 10, 20, 30
10A, 10, 20, 30
Stop–M, Stop–A, Ind
No, Yes
3,0 – 8,0
x Ie
0,2 – 10,0
Sec
Stop–M, Stop–A, Ind
No, Yes
0,4 – 0,8
x Ie
1 – 30
Sec
Stop–M, Stop–A, Ind
No, Yes
10 – 80
%
Stop–M, Stop–A, Ind
No, Yes
Stop–M, Stop–A, Ind
No, Yes
Stop–M, Stop–A, Ind
No, Yes