6 DEDICATED INSTRUCTIONS
Send data
Device
(S2) + 0
to
Send data
(S2) + n
Functions
CPU module
MSEND "Un" (S1) (S2) (D)
CPU module
MSEND "Un" (S1) (S2) (D)
6 - 10
Item
Designate the contents of e-mail ((Subject + attached
file) or (Subject + main text)) to be sent.
2 The "Set by" column indicates the following:
• User: Data is set by the user before executing a dedicated instruction.
• System: The programmable controller CPU stores the execution result of a
dedicated instruction.
3 For a list of error codes, see the User's Manual (Basic).
(1) This instruction sends mails to the designated external device.
(a) When sending data as an attached file
(b) When sending data as main text
(2) Whether the MSEND instruction is being executed or has been completed
normally or abnormally can be checked with the completion device (D) or
completion status display flag ((D) + 1) designated in the set data.
(a) Completion device (D)
Turns on at the END processing of the scan where the MSEND instruction is
completed, and turns off at the next END processing.
(b) Status display device at completion ((D) + 1)
Turns on and off depending on the completion status of the MSEND instruction.
Normal completion: Stays off and does not change.
Abnormal completion: Turns on at the END processing of the scan where
Set data
Ethernet module
Transmission destination
number = mail address
Ethernet module
Transmission destination
number = mail address
the MSEND instruction is completed, and turns off at
the next END processing.
MELSEC-Q/L
Setting range
Mail server
Send destination mail
address
Subject
Main Text
Attached file
Attached file name=
mmddhhss.bin
Mail server
Send destination mail
address
Subject
Main text
2
Set by (
)
User
6 - 10