10 Extended Function Relevant Error List

(1) Error occurred when MELFA-BASIC IV is selected while shared memory extended function is valid
Error No
L3994
Error message
Cause
Measure
(2) Error occurred when the parameter ALWENA is set to one (enabled) while the sequencer direct perfor-
mance is valid
Error No
L3995
Error message
Cause
Measure
(3) Error occurred when MELFA-BASIC IV is selected while the sequencer direct performance is valid
Error No
L3996
Error message
Cause
Measure
Error Cause and Measure
Shared memory extended function unavailable (MB4)
Shared memory extended function is unavailable in MELFA-BASIC IV.
The parameter RLNG=1 (MELFA-BASIC IV) is selected while shared memory extended function
is valid. Make sure to set the parameter RLNG to 2 (MELFA-BASIC V).
Set the parameter RLNG to 2 (MELFA-BASIC V).
Error Cause and Measure
Unavailable together with the function (sequencer direct, ALWENA)
Unavailable together with the function (sequencer direct, ALWENA)
The parameter ALWENA is set to one (enabled) while the sequencer direct performance function
is valid. During performing sequencer direct, X** commands are unavailable in the always run-
ning program. Make sure to set the parameter ALWENA to zero (disabled).
Set the parameter ALWENA to zero (disabled).
Error Cause and Measure
Sequencer direct function unavailable (MB4)
Sequencer direct function is unavailable in MELFA-BASIC IV.
The parameter RLNG=1 (MELFA-BASIC IV) is selected while the sequencer direct perfor-
mance function is valid. Make sure to set the parameter RLNG to 2 (MELFA-BASIC V).
Set the parameter RLNG to 2 (MELFA-BASIC V).
10Extended Function Relevant Error List
10-118