380…480 Volt, Fuse Requirements - ABB ACH580 Series Installation, Operation And Maintenance Manual

Hide thumbs Also See for ACH580 Series:
Table of Contents

Advertisement

ACH580 Installation, Operation and Maintenance Manual
380...480 volt, fuse requirements
ACH580-01-
02A1-4
0340-4
03A5-4
04A8-4
07A6-4
012A-4
014A-4
023A-4
027A-4
034A-4
044A-4
052A-4
065A-4
077A-4
096A-4
124A-4
156A-4
180A-4
240A-4
302A-4
361A-4
414A-4
1) ABB does not require Bussmann brand fuses. Fuses which meet the appropriate UL class type,
current rating, and are rated at 600V, 200 kA may be used.
Input
Maximum
current
Voltage rating
current
A
A
3-phase U
2.1
15
3.0
15
3.5
15
4.8
15
7.6
15
12.0
15
14.0
30
23.0
30
27.0
40
34.0
60
44.0
60
52
80
62
100
77
100
106
150
124
200
156
225
180
300
240
350
302
500
361
500
414
600
UL
Bussmannn type
V
= 460 V
N
600
JJS-15
600
JJS-15
600
JJS-15
600
JJS-15
600
JJS-15
600
JJS-15
600
JJS-30
600
JJS-30
600
JJS-40
600
JJS-60
600
JJS-60
600
JJS-80
600
JJS-100
600
JJS-100
600
JJS-150
600
JJS-200
600
JJS-225
600
JJS-300
600
JJS-350
600
JJS-500
600
JJS-500
600
JJS-600
25
1
UL class
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T