208 Volt Fuses For Packaged Drive - ABB ACH580 Series Installation, Operation And Maintenance Manual

Hide thumbs Also See for ACH580 Series:
Table of Contents

Advertisement

ACH580 Installation, Operation and Maintenance Manual
Branch circuit protection
Input power is connected to the ACH580 with E-Clipse Bypass through a door
interlocked disconnect switch or circuit breaker. Neither of these inputs are fused.
The branch circuit that provides power to the ACH580 with E-Clipse Bypass with
disconnect switch must include the specified external fuses to provide short circuit
and ground fault protection for the motor in the bypass mode.
When connected to a 240V or 480V power source, the ACH580 with E-Clipse
Bypass with the circuit breaker option is suitable for use on a circuit capable of
delivering not more than 100,000 RMS symmetrical amperes. When connected to a
600V power source, PCR configurations are suitable for use on a circuit capable of
delivering not more than 10,000 RMS symmetrical amperes (75-150 HP), and not
more than 25,000 RMS symmetrical amperes (2-60 HP).
Fuses
Note: The UL listed drive fuses in the table are provided in the purchased product.
• Replacement fuses are required to be of the same class, current rating, and
voltage rating. Fuses from other manufacturers can be used if they are 600V
rated and meet the specifications given in the table.
• Fuses with higher current rating than specified must not be used.

208 Volt fuses for packaged drive

Type Code
ACH580-PxR-04A6-2
ACH580-PxR-06A6-2
ACH580-PxR-07A5-2
ACH580-PxR-10A6-2
ACH580-PxR-017A-2
ACH580-PxR-024A-2
ACH580-PxR-031A-2
ACH580-PxR-046A-2
ACH580-PxR-059A-2
ACH580-PxR-075A-2
ACH580-PxR-088A-2
ACH580-PxR-114A-2
ACH580-PxR-144A-2
ACH580-PxR-169A-2
ACH580-PxR-211A-2
ACH580-PxR-248A-2
1) "PxR" represents both PCR and PDR.
2) 100 HP @ 230V
Nominal Output
208 Volt
Range
Drive
Packag
Current
e Power
1
A
4.6
6.6
7.5
10.6
16.7
24.2
30.8
46.2
59.4
74.8
88
114
143
169
211
248
Internal Drive
Base
Fuse Rating
Drive
Frame
Size
HP
Class
1
R1
Class CC
1.5
R1
Class CC
2
R1
Class CC
3
R1
Class CC
5
R1
Class CC
7.5
R2
Class CC
10
R2
Class T
15
R3
Class T
20
R3
Class T
25
R4
Class T
30
R5
Class T
40
R5
Class T
50
R6
Class T
60
R7
Class T
75
R7
Class T
2
100
R8
Class T
External Fuse for
Disconnect Option
Current
Class
Rating
15A
N/A
15A
N/A
15A
N/A
15A
N/A
30A
N/A
30A
N/A
40A
N/A
80A
N/A
80A
N/A
100A
N/A
110A
N/A
150A
N/A
200A
N/A
250A
N/A
300A
Class J or RK1
350A
Class J or RK1
ACH580-PCR/PDR
145
Max Current
Rating
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
400A
400A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents