Install The Control Wiring; Basic Connections - ABB ACH580 Series Installation, Operation And Maintenance Manual

Hide thumbs Also See for ACH580 Series:
Table of Contents

Advertisement

ACH580 Installation, Operation and Maintenance Manual

Install the control wiring

Connect control wiring to terminal block X1 on the ACH580 control board and to
terminal block X2 on the E-Clipse Bypass control board. For more information on
these connections, refer to the following:
• X1 terminal block location and terminal data are defined in the
instructions for the drive on page 40.
• X2 terminal block location is illustrated in the figures starting with
diagrams – Vertical E-Clipse Bypass
• X2 terminal data are provided in
Default
• Basic connections are described in the following paragraphs. Alternate
configurations using the E-Clipse Bypass macro are described in the ACH580
HVAC control program firmware manual.
• On Terminal Block X1 inside the ACH580, analog inputs and outputs and
additional digital input and relay output connections (AI1, AI2, AO1, AO2,
DI1...DI6 and RO1...RO6) are available for use.
Note: The E-Clipse Bypass control circuitry uses serial communications connections
(X1:29...X1:31) inside the ACH580. These connections are not available for any
other purpose and must not be reconfigured.
Digital I/O
control
terminals
J2
connection
GND J6
on page 108.
BYPASS CONTROL
ESC
ENTER
ENABLED
HAND
SELECTED
FAULTED
DRIVE
BYPASS
OFF/RESET
AUTO
MOTOR RUN
EIA-485
terminals
connection
Bottom view
connection
on page 91.
Basic control connections for E-Clipse HVAC

Basic connections

The figure on page
control connections for use with the
E-Clipse Bypass HVAC Default macro.
These connections are described in the
following paragraphs.
In typical installations, only analog input
wires connect to the ACH580 terminal
block, with other control connections
made on the E-Clipse Bypass control
board.
Use wire ties to permanently affix control/
port
communications wiring to the hooked wire
control
race tie points provided, maintaining a
minimum 6 mm (1/4 in.) spacing from
power wiring.
J7
J8
99
Installation
Connection
108
shows the basic