Power Wiring Torque Table - ABB ACH580 Series Installation, Operation And Maintenance Manual

Hide thumbs Also See for ACH580 Series:
Table of Contents

Advertisement

30
12. Connect the ground screen pig-tail for Embedded fieldbus, EFB (EIA-485) cables at
X5. (Ground only at drive end.)
13. Strip and connect the individual control wires to the drive terminals. Tighten the
screws to 0.4 lb-ft (0.5...0.6 N•m).
WARNING! To avoid danger or damage to the drive on IT systems and corner
grounded TN systems, see section
and corner-grounded TN systems (North America)
Typical Type 1
1
9

Power wiring torque table

Frame size
T1/U, T2/V, T3/W
L1, L2, L3
R+, R-
PE Ground
ACH580-01 Installation
R1...R2
Relay Outputs
VAR
6
lb-ft
0.7
0.7
0.7
1.1
ACH580 Installation, Operation and Maintenance Manual
Checking the compatibility with IT (ungrounded)
on page 17.
Analog Inputs
and Outputs
Option Mounting
Digital
Inputs
EMC
7
5
1
9
R1
N•m
lb-ft
1.0
1.1
1.0
1.1
1.0
1.1
1.5
1.1
8C
8B
8A
R2
N•m
1.5
1.5
1.5
1.5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents