Cable entries

Input, motor and brake resistor cable terminal sizes (per phase) and tightening
torques are given below. For units without enclosure extension, one hole cable lugs
(1/2 inch diameter) can be used. The maximum allowed width of the cable lug is
1.5 inches. For units with enclosure extension, two hole cable lugs (1/2 inch
diameter) can be used.
Frame
size
R7
R8

Dimensions, weights and noise

Frame size
R7
R8
H
height without lifting lugs
W1 width of the basic unit
W2 width with the optional enclosure extension
W3 weight of the basic unit
W4 weight with the optional enclosure extension (basic configuration with switch fuse but without
contactor and other options).
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
U1, V1, W1, U2, V2, W2, UDC+/R+, UDC-, R- Grounding PE
Screw
Tightening torque
1/2
1/2
UL type 1
H1
W1
in.
in.
59.31
9.82
79.67
13.66
Screw
lbf ft
37...55
5/16
37...55
5/16
W2
Depth
in.
in.
23.70
20.65
31.24
24.47
Tightening torque
lbf ft
11...16
11...16
W3
W4
Noise
lb
lb
dB
243
430
71
529
827
72