... 6 Electrical connections

Conductor cross-section on electronic unit

Note
Detailed information on separate electronic units can be found
in the corresponding data sheets.
EAN823 – Screw terminals
Motor/brake
Mains
Signals
EBN853 – Screw terminals
Motor/brake
Mains
Signals
EBN861 – Screw terminals
Motor/brake
Mains
Signals
EAS822 – Clamping connection
Mains cable
Signal cable (DCS)
Transmitter (option)
Motor cable
Sensor cable
EBS852 – Clamping connection
Mains cable
Signal cable (DCS)
Transmitter (option)
Motor cable
Sensor cable
2
fixed: 1.5 to 6 mm
(16 to 10 AWG)
2
flexible: 1.5 to 4 mm
(16 to 12 AWG)
2
fixed: 0.5 to 6 mm
(20 to 10 AWG)
2
flexible: 0.5 to 4 mm
(20 to 12 AWG)
2
fixed: 0.5 to 6 mm
(20 to 10 AWG)
2
flexible: 0.5 to 4 mm
(20 to 12 AWG)
2
fixed: 1.5 to 6 mm
(16 to 10 AWG)
2
flexible: 0.2 to 4 mm
(24 to 12 AWG)
2
fixed: 1.5 to 6 mm
(16 to 10 AWG)
2
flexible: 0.5 to 4 mm
(20 to 12 AWG)
2
fixed: 0.5 to 4 mm
(20 to 12 AWG)
2
flexible: 0.5 to 2.5 mm
(20 to 14 AWG)
2
fixed: 1.5 to 6 mm
(16 to 10 AWG)
2
flexible: 1.5 to 4 mm
(16 to 12 AWG)
2
fixed: 0.5 to 6 mm
(20 to 10 AWG)
2
flexible: 0.5 to 4 mm
(20 to 12 AWG)
2
fixed: 0.5 to 4 mm
(20 to 12 AWG)
2
flexible: 0.5 to 2.5 mm
(20 to 14 AWG)
Suited for cable Ø Terminals for conductor
cross-section
13 mm (0.51 in)
max. 4 mm
8 mm (0.31 in)
max. 1.5 mm
8 mm (0.31 in)
max. 1.5 mm
13 mm (0.51 in)
max. 4 mm
8 mm (0.31 in)
max. 1.5 mm
Suited for cable Ø Terminals for conductor
cross-section
13 mm (0.51 in)
max. 4 mm
8 mm (0.31 in)
max. 1.5 mm
8 mm (0.31 in)
max. 1.5 mm
13 mm (0.51 in)
max. 4 mm
8 mm (0.31 in)
max. 1.5 mm
EBS862 – Clamping connection
Mains cable
Signal cable (DCS)
Transmitter (option)
Motor cable
Sensor cable

Cable glands

The actuators and electronic units are supplied without cable
glands. Suited cable glands must be installed on site.
Tap holes for cable glands
Signals
Motor
*
Adapter for PG or NPT thread must be ordered separately

Selection of suited connection cables

Please observe the following information when selecting cables:
Use shielded cables for the motor/brake cable, the sensor
cable, and the signal cable to the control system/controller.
Connect the shielding of the motor/brake cable and the
sensor cable on both sides (to the actuator and to the
Contrac electronic unit).

Potential equalization

In order to avoid the risk of an electric shock, it must not be
2
(12 AWG)
possible to come into contact with dangerous live parts and
2
(16 AWG)
conductive parts that can be touched should not become
2
(16 AWG)
dangerous live parts either under standard conditions or under
2
(12 AWG)
conditions when a single fault occurs.
2
(16 AWG)
The actual current flowing in the event of a fault is obtained
from the phase to ground voltage and the total impedance
present in the fault circuit.
For long cables, the voltage drop may be dangerous to come
into contact with high current flowing.
Preferably, the electronic unit and the actuator must be
2
(12 AWG)
connected with low resistance (ground resistance < 0.1 Ω) to the
2
(16 AWG)
potential equalization.
2
(16 AWG)
In the process, the respective standards of the VDE 100 series
2
(12 AWG)
must be observed.
2
(16 AWG)
Terminals for conductor cross-section
metric
optional adapters for*
M20 × 1.5 (2 ×)
PG 16 (2 ×)
M25 × 1.5 (1 ×)
PG 21 (1 ×)
2
max. 6 mm
(10 AWG)
2
max. 4 mm
(12 AWG)
2
max. 4 mm
(12 AWG)
2
max. 6 mm
(10 AWG)
2
max. 4 mm
(12 AWG)
NPT ½ in (2 ×)
NPT ¾ in (1 ×)