Connecting the power cables
Refer to
screw can be used for connecting two cable lugs (on both sides of the busbar).
Connecting the power cables of units without EMC filter +E202. Frame sizes R7 and R8.
Step
1
Lead the cables into the cubicle through the cable entries provided.
Note: 360 degrees grounding is not needed at the cable entry. The short twisted shield provides, in addition to the
protective grounding, also sufficient disturbance suppression.
2
Slide the grommets onto the cables.
3
Cut the cables to appropriate length.
4
Terminate the conductors with cable lugs or connectors.
5
Connect the cable shields to the PE busbar.
6
Connect the phase conductors of the motor cable to the U2, V2 and W2 terminals.
7
Connect the phase conductors of the supply cable to the U1, V1 and W1 terminals.
8
Connect the optional brake conductors to the R+ and R- terminals.
Connecting the power cables of units with EMC filter +E202. Frame size R7 with bottom entry and exit.
Step
Instruction
1
Remove the shroud in front of the
input terminals.
2
Remove the EMC screen by
undoing the fastenings screws:
one at the right side, three behind
the input terminals.