ABB ACS800 Hardware Manual page 71

45 / 60 to 560 / 600 kw
Hide thumbs Also See for ACS800:
Table of Contents

Advertisement

Connecting the power cables of units with EMC filter +E202. Frame size R7 with top entry and exit.
Step
Instruction
11
It is recommended to make a 360
degrees grounding for the input
cable in the same way as for the
motor cable.
12
Connect the twisted shield of the
input cable to the PE busbar of
the cabinet.
13
Connect the phase conductors of
the input cable to the U1, V1 and
W1 terminals.
14
Fasten the shroud.
Connecting the power cables of units with EMC filter +E202. Frame size R8 with bottom entry and exit.
Step
Instruction
1
Remove the shroud in front of the
input terminals.
2
Remove the EMC screen by
undoing the 9 fastening screws
and 1 fastening nut.
Note: When refitting the screen,
first fasten screws
the rest of the screws.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
, then
I
II
III
Photo
12
PE
13
13
13
U1
V1
W1
Photo
2
10
I
EMC screen removed
71
II
III
Installation