Cable Types; Cable Entries; Dimensions, Weights And Noise - ABB ACS800 Hardware Manual

Hide thumbs Also See for ACS800:
Table of Contents

Advertisement

Cable types

The table below gives copper and aluminium cable types for different load currents.
Cable sizing is based on max. 9 cables laid on a cable ladder side by side, ambient
temperature 30°C, PVC insulation, surface temperature 70°C (EN 60204-1 and
IEC 60364-5-2/2001). For other conditions, size the cables according to local safety
regulations, appropriate input voltage and the load current of the drive.
Copper cables with concentric
Max. load
current
119
153
186
215
249
284

Cable entries

Mains, DC link and motor cable terminal sizes (per phase), accepted cable
diameters and tightening torques are given below
Frame size
R5
R6
* with cable lugs 16...70 mm

Dimensions, weights and noise

Frame size
R5
R6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
copper shield
Cable type
2
A
mm
34
3x6
47
3x10
62
3x16
79
3x25
98
3x35
3x50
3x70
3x95
3x120
3x150
3x185
U1, V1, W1, U2, V2, W2, UDC+,UDC
Wire size
2
mm
6...70
95...185 *
2
, tightening torque 20...40 Nm
Height
mm
816
970
Aluminium cables with concentric
copper shield
Max. load
Cable type
current
A
mm
61
3x25
75
3x35
91
3x50
117
3x70
143
3x95
165
3x120
191
3x150
PDM code: 00096931-C
Max. cable Ø
IP21
mm
35
53
IP21
Width
Depth
mm
mm
265
390
300
439
2
.
-
Earthing PE
Tightening
Wire size
torque
2
Nm
mm
10
6...70
20...40
16...95
Weight
kg
65
100
Technical data
105
Tightening
torque
Nm
15
8
Noise
dB
70
73

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs800-31Acs800-u31

Table of Contents