ABB ACS800 Hardware Manual page 33

45 / 60 to 560 / 600 kw
Hide thumbs Also See for ACS800:
Table of Contents

Advertisement

Motor type
Nominal mains
voltage (AC line
voltage)
N
Random-
U
< 420 V
N
wound and
O
form-wound
N
420 V < U
-
A
B
B
500 V < U
600 V < U
*
manufactured before 1.1.1998
** For motors manufactured before 1.1.1998, check for additional instructions with the motor manufacturer.
*** If the intermediate DC circuit voltage of the drive is increased from the nominal level by resistor braking or by the
IGBT Supply Control Program (parameter selectable function), check with the motor manufacturer if additional
output filters are needed in the applied drive operation range.
Note 1: The abbreviations used in the table are defined below.
Abbreviation
Definition
U
nominal voltage of the supply network
N
Û
peak line-to-line voltage at motor terminals which the motor insulation must withstand
LL
P
motor nominal power
N
du/dt
du/dt filter at the output of the drive +E205
CMF
common mode filter +E208
N
N-end bearing: insulated motor non-drive end bearing
n.a.
Motors of this power range are not available as standard units. Consult the motor manufacturer.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Motor insulation
system
Standard: Û
=
LL
1300 V
< 500 V Standard: Û
=
N
LL
1300 V
or
Reinforced: Û
=
LL
1600 V, 0.2
microsecond rise
time
< 600 V Reinforced: Û
=
N
LL
1600 V
or
Reinforced: Û
=
LL
1800 V
< 690 V Reinforced: Û
=
N
LL
1800 V
Reinforced: Û
=
LL
2000 V, 0.3
microsecond rise
time ***
Requirement for
ABB du/dt filter, insulated N-end bearing and ABB common mode
P
< 100 kW
100 kW < P
N
and
frame size > IEC 315
frame size < IEC 315
P
< 134 HP
134 HP < P
N
and frame size <
or frame size >
NEMA 500
-
+ N or CMF
+ du/dt
+ du/dt + N
or
+ du/dt + CMF
-
+ N or CMF
+ du/dt
+ du/dt + N
or
+ du/dt + CMF
-
+ N or CMF
+ du/dt
+ du/dt + N
-
N + CMF
filter
< 350 kW
P
> 350 kW
N
N
or
frame size > IEC 400
< 469 HP
P
> 469 HP
N
N
or frame size >
NEMA 500
NEMA 580
+ N + CMF
+ du/dt + N + CMF
+ N + CMF
+ du/dt + N + CMF
+ N + CMF
+ du/dt + N + CMF
N + CMF
Planning the electrical installation
33
or

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs800-02Acs800-u2

Table of Contents