Cc-Link Ie Tsn Communication Function Setting; Ip Address Setting - Mitsubishi Electric CC-Link IE TSN FR-A8NCG Instruction Manual

Table of Contents

Advertisement

5.6

CC-Link IE TSN communication function setting

5.6.1

IP address setting

For CC-Link IE TSN communication, the IP address of the inverter is set using the station number switches on the circuit board
of the FR-A8NCG or inverter parameters. Note that the station number switch setting has a higher priority than the parameter
setting (when the station number switch settings are "1 to 254").
For CC-Link IE TSN communication, the third octet of the inverter's IP address is used as the network No. and the fourth octet
is used as the station number. (Enter the IP address assigned by the network administrator.)
 Setting the IP address with the station number switches
Set a value other than "0 (H00)" or "255 (HFF)" to specify a station number using the station number switches. The setting
range is from "1 (H01)" to "254 (HFE)". The setting is applied after an inverter reset or at the next power-ON.
IP address
First octet
The settings of the master station are used. (The settings from Pr.434 to
Second octet
Pr.436 are invalid.)
Third octet
The station number switch setting is enabled regardless of the setting in
Fourth octet
Pr.437.
Set the arrow () of each switch to the number or letter (0-9, A-F) corresponding to the desired station number.
• Setting example
Setting for station number 1 (H01):
Set the arrow () of X16 to "0" and the arrow () of
X1 to "1".
48
INVERTER SETTING
Description
Setting for station number 254 (HFE):
Set the arrow () of X16 to "F" and the arrow () of
X1 to "E".
X16
X1
X16
X1

Advertisement

Table of Contents
loading

This manual is also suitable for:

800 series

Table of Contents