ABB i-bus KNX Product Manual page 48

Time receiver gps, tr/a 1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Delay darkness in [s]
Options:
The parameter is used to define a delay for falling below the parameterized threshold. Switchover takes
place only after the threshold (plus hysteresis) has been fallen below for the parameterized time.
This serves to prevent brief dimming from causing unnecessary switching.
Delay brightness in [s]
Options:
The parameter is used to define a delay for exceeding the parameterized threshold. Switchover takes
place only after the threshold (plus hysteresis) has been exceeded for the parameterized time. This serves
to prevent brief illumination (e.g. by car headlights) from causing unnecessary switching.
Switching bit or scene
Options:
46 2CDC509082D0201 | TR/A 1.1
0 ... 60 ... 3,600
0 ... 60 ... 3,600
Switching bit
Scene
Switching bit: The 1-bit object Sends light above/below threshold 1 – Sending is enabled. The object
value changes according to the reaction parameterized in the Lux logic parameter in the Light control
parameter window.
Scene: The 1-byte object Sends scene light above/below threshold 1 – Sending is enabled.
The following parameters are enabled.
Scene number for switching on
Options: 1 ... 64
The scene selected here is sent on switch-on.
Scene number for switching off
Options: 1 ... 64
The scene selected here is sent on switch-off.