88
Parameters in the Long Parameter mode
Index Name/Selection
2205
ACCELER TIME 2
0.0...1800.0 s
2206
DECELER TIME 2
0.0...1800.0 s
2207
RAMP SHAPE 2
0.0...1000.0 s
2208
EMER DEC TIME
0.0...1800.0 s
2209
RAMP INPUT 0
0 = NOT SEL
1 = DI1
2 = DI2
3 = DI3
4 = DI4
5 = DI5
-1 = DI1(INV)
-2 = DI2(INV)
-3 = DI3(INV)
-4 = DI4(INV)
-5 = DI5(INV)
Actual signals and parameters
Description
Defines the acceleration time 2 i.e. the time required for the speed to change
from zero to the speed defined by parameter
See parameter
2202
ACCELER TIME 1.
Acceleration time 2 is used also as jogging acceleration time. See parameter
1010
JOGGING SEL.
Time
Defines the deceleration time 2 i.e. the time required for the speed to change
from the value defined by parameter
See parameter
2203
DECELER TIME 1.
Deceleration time 2 is used also as jogging deceleration time. See parameter
1010
JOGGING SEL.
Time
Selects the shape of the acceleration/deceleration ramp 2. The function is
deactivated during emergency stop
Ramp shape 2 is used also as jogging ramp shape time. See parameter
JOGGING SEL.
See parameter
2204
RAMP SHAPE 1.
Defines the time within the drive is stopped if an emergency stop is activated.
See parameter
2109
EMER STOP SEL.
Time
Defines the source for forcing the ramp input to zero.
Not selected
Digital input DI1.1 = ramp input is forced to zero. Ramp output will ramp to
zero according to the used ramp time.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
Inverted digital input DI1.0 = ramp input is forced to zero. Ramp output will
ramp to zero according to the used ramp time.
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
2008
MAXIMUM FREQ.
2008
MAXIMUM FREQ to zero.
(2109
EMER STOP SEL).
Def
60
60
0
1010
1
0 = NOT SEL