Ul Marking; Ul Checklist; Iec/En 61800-3 (2004) Definitions; Select - ABB ACS150 User Manual

0.37...4 kw, 0.5...5 hp
Table of Contents

Advertisement

UL marking

See the type designation label for the valid markings of your drive.

UL checklist

Input power connection – See section
Disconnecting device (disconnecting means) – See section
page 23.
Ambient conditions – The drives are to be used in a heated indoor controlled environment. See
section
Input cable fuses – For installation in the United States, branch circuit protection must be provided in
accordance with the National Electrical Code (NEC) and any applicable local codes. To fulfil this
requirement, use the UL classified fuses given in section
For installation in Canada, branch circuit protection must be provided in accordance with Canadian
Electrical Code and any applicable provincial codes. To fulfil this requirement, use the UL classified
fuses given in section
Power cable selection – See section
Power cable connections – For the connection diagram and tightening torques, see section
Connecting the power cables
Overload protection – The drive provides overload protection in accordance with the National
Electrical Code (US).
Braking – The drive has an internal brake chopper. When applied with appropriately sized brake
resistors, the brake chopper will allow the drive to dissipate regenerative energy (normally associated
with quickly decelerating a motor). Brake resistor selection is discussed in section
page 125.

IEC/EN 61800-3 (2004) Definitions

EMC stands for Electromagnetic Compatibility. It is the ability of electrical/electronic equipment to
operate without problems within an electromagnetic environment. Likewise, the equipment must not
disturb or interfere with any other product or system within its locality.
First environment includes establishments connected to a low-voltage network which supplies buildings
used for domestic purposes.
Second environment includes establishments connected to a network not directly supplying domestic
premises.
Drive of category C2: drive of rated voltage less than 1000 V and intended to be installed and
commissioned only by a professional when used in the first environment. Note: A professional is a
person or organisation having necessary skills in installing and/or commissioning power drive systems,
including their EMC aspects.
Category C2 has the same EMC emission limits as the earlier class first environment restricted
distribution. EMC standard IEC/EN 61800-3 does not any more restrict the distribution of the drive, but
the using, installation and commissioning are defined.
Drive of category C3: drive of rated voltage less than 1000 V, intended for use in the second
environment and not intended for use in the first environment.
Category C3 has the same EMC emission limits as the earlier class second environment unrestricted
distribution.
Ambient conditions
on page
Power cable sizes and fuses
on page 32.
Input power connection
121
for specific limits.
Power cable sizes and fuses
on page 116.
Selecting the power cables
on page 119.
Supply disconnecting device
on page 116.
on page 26.
Brake resistors
Technical data
123
on
on

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs350

Table of Contents