Parameters in the Long Parameter mode

The following table includes the complete descriptions of all parameters that are
visible only in the Long Parameter mode. See section
for how to select the parameter mode.
Parameters in the Long Parameter mode
Index Name/Selection

10 START/STOP/DIR

1001
EXT1 COMMANDS
0 = NOT SEL
1 = DI1
2 = DI1,2
3 = DI1P,2P
4 = DI1P,2P,3
5 = DI1P,2P,3P
8 = KEYPAD
9 = DI1F,2R
20 = DI5
21 = DI5,4
1002
EXT2 COMMANDS
1003
DIRECTION
Actual signals and parameters
Description
The sources for external start, stop and direction control
Defines the connections and the source for the start, stop and direction
commands for external control location 1 (EXT1).
No start, stop and direction command source
Start and stop through digital input DI1. 0 = stop, 1 = start. Direction is fixed
according to parameter
1003
Start and stop through digital input DI1. 0 = stop, 1 = start. Direction through
digital input DI2. 0 = forward, 1 = reverse. To control direction, parameter
1003
DIRECTION setting must be REQUEST.
Pulse start through digital input DI1. 0 -> 1: Start. (In order to start the drive,
digital input DI2 must be activated prior to the pulse fed to DI1.)
Pulse stop through digital input DI2. 1 -> 0: Stop. Direction of rotation is fixed
according to parameter
1003
Pulse start through digital input DI1. 0 -> 1: Start. (In order to start the drive,
digital input DI2 must be activated prior to the pulse fed to DI1.)
Pulse stop through digital input DI2. 1 -> 0: Stop. Direction through digital
input DI3. 0 = forward, 1 = reverse. To control direction, parameter
DIRECTION setting must be REQUEST.
Pulse start forward through digital input DI1. 0 -> 1: Start forward. Pulse start
reverse through digital input DI2. 0 -> 1: Start reverse. (In order to start the
drive, digital input DI3 must be activated prior to the pulse fed to DI1/DI2).
Pulse stop through digital input DI3. 1 -> 0: Stop. To control the direction,
parameter
1003
DIRECTION setting must be REQUEST.
Start, stop and direction commands through control panel when EXT1 is
active. To control the direction, parameter
REQUEST.
Start, stop and direction commands through digital inputs DI1 and DI2.
DI1
DI2 Operation
0
0
Stop
1
0
Start forward
0
1
Start reverse
1
1
Stop
Parameter
1003
DIRECTION setting must be REQUEST.
Start and stop through digital input DI5. 0 = stop, 1 = start. Direction is fixed
according to parameter
1003
Start and stop through digital input DI5. 0 = stop, 1 = start. Direction through
digital input DI4. 0 = forward, 1 = reverse. To control direction, parameter
1003
DIRECTION setting must be REQUEST.
Defines the connections and the source for the start, stop and direction
commands for external control location 2 (EXT2).
See parameter
1001
EXT1 COMMANDS.
Enables the control of rotation direction of the motor, or fixes the direction.
Parameter modes
DIRECTION (setting REQUEST = FORWARD).
DIRECTION (setting REQUEST = FORWARD).
1003
DIRECTION setting must be
DIRECTION (setting REQUEST = FORWARD).
on page
53
Def
2 = DI1,2
1003
0 = NOT SEL
3 =
REQUEST