Input And Output Module Io204; Description - Siemens SIPROTEC 5 Series Hardware Description

Table of Contents

Advertisement

[tdio203x-110313-01.tif, 1, en_US]
Figure 3-21

Input and Output Module IO204

3.2.5
3.2.5.1

Description

The terminals for the following are located on the input and output module IO204:
10 binary inputs
4 binary outputs with 4 standard make contacts (type S)
4 power relays for controlling 2 motors (forward/backward) with a common auxiliary voltage supply V
+, V
-
aux
The power relays operate in interlocked mode, that is, only one relay of each switching pair picks up at a
time thereby avoiding a power-supply short circuit. Note the polarity specified in the terminal and
connection diagram.
The connections are distributed over three 14-pole voltage terminals.
SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-C, Edition 10.2017
IO203 – Connection Diagram
3.2 Input and Output Modules of the Modular Devices
Electronic Modules
aux
63