Communication Applications Of The Plug-In Modules - Siemens SIPROTEC 5 Series Hardware Description

Table of Contents

Advertisement

Plug-In Modules
4.2 Communication Modules
Ethernet Modules
Application: Ethernet-based communication to the substation automation technology via substation-
control protocols (for example, IEC 61850 and DNP3)
Secure communication to DIGSI 5
Communication between the devices (IEC 61850-GOOSE)
Synchrophasor protocol
The modules can be operated with or without an integrated switch.
Long-distance modules
Application: Direct protection interface communication over long distances using multimode or single-
mode optical fibers.
The designation of the modules corresponds to the following scheme, which is typically explained with the
module USART-AB-1EL. The module designation consists of 3 blocks.
1st block
2nd block
3rd block

Communication Applications of the Plug-In Modules

4.2.2
You can find information on communication applications for the plug-in modules in the following tables.
Table 4-1
Plug-In Module
Physical Connection
1 x electrical serial RS485, RJ45
2 x electrical serial RS485, RJ45
1 x optical serial, 820 nm, ST connector,
2 km via 62.5/125 μm multimode optical
fiber
132
Type of module
USART = Serial module for short or long distance
ETH = Ethernet module
Unique code for the module in the product code of the device
The code consists of 2 letters.
Number and physical design of the connections
1 = 1 connection (1 channel)
2 = 2 connections (2 channels)
EL = Electrical connection
FO = Fiber-optic connection
LDFO = Long-distance transmission via optical fibers
Communication Applications of the Plug-In Modules
SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-C, Edition 10.2017

Hide quick links: