Reference Conditions And Influencing Variables - Siemens SIPROTEC 5 Series Hardware Description

Table of Contents

Advertisement

6.11

Reference Conditions and Influencing Variables

Reference Conditions
Measurand current I
Measurand voltage V
Frequency f
Sine waveform, total harmonic distortion
Ambient temperature T
Auxiliary voltage V
Warmup time
External fields/external influences
Variables Influencing Pickup and Dropout Thresholds (Protection)
Auxiliary voltage: 0.8 V
Ambient temperature: -10 °C to 55 °C
Frequency: 45 Hz to 65 Hz
Harmonics
Up to 10 % of 3rd harmonics
Up to 10 % of 5th harmonics
Warmup
Transient excess pickup in fundamental component measurement
method for τ > 100 ms (with complete unbalance)
EMC interference
Variables Influencing the Measured Values (Fault Recorders)
Auxiliary voltage: 0.8 V
Ambient temperature: -10 °C to 55 °C
Frequency: 45 Hz to 65 Hz
Harmonics
Up to 10 % of 3rd harmonics
Up to 10 % of 5th harmonics
Warmup
Transient excess pickup in fundamental component measurement
method for τ > 100 ms (with complete unbalance)
EMC interference
12
Use shielded cables for the current and voltage measuring inputs on the fault recorder.
SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-C, Edition 10.2017
a
a
to 1.2 V
ar
ar
to 1.2 V
ar
ar
12
6.11 Reference Conditions and Influencing Variables
I
± 1 %
rated
V
± 1 %
rated
f
± 1 %
rated
≤ 5 %
23 °C ± 1 °C/73.4 °F ± 2 °F
V
± 1 %
auxrated
≥ 15 min
None
≤ 0.2 %
≤ 0.5 %/10 K
≤ 1 %
≤ 1 %
≤ 1 %
≤ 0.3 %
≤ 5 %
≤ 5 %
≤ 0.2 %
≤ 0.5 %/10 K
≤ 1 %
≤ 1 %
≤ 1 %
≤ 0.3 %
≤ 5 %
≤ 1.5 %
Technical Data
209