Input And Output Modules Of The Non-Modular Devices (7Xx82); Function Description Of The Input And Output Modules Of The Non-Modular Devices; Input And Output Module Io101; Description - Siemens SIPROTEC 5 Series Hardware Description

Table of Contents

Advertisement

Electronic Modules

3.4 Input and Output Modules of the Non-Modular Devices (7xx82)

3.4
Input and Output Modules of the Non-Modular Devices (7xx82)
Function Description of the Input and Output Modules of the Non-Modular
3.4.1
Devices
Module Designation
IO101
IO102
IO103
IO110
IO111

Input and Output Module IO101

3.4.2
3.4.2.1

Description

The terminals for the following are located on the input and output module IO101:
4 current transformers (3 transformers always as protection-class current transformers, the 4th optionally
as protection-class or instrument transformer)
8 binary inputs
6 binary outputs, of which:
4 standard make contacts (type S)
2 standard change-over contacts (type S)
The connections are distributed over:
1 x 8-pole current terminal
2 x 14-pole voltage terminal
108
Function Description
Input and output module
4 current measuring inputs, 8 binary inputs, 6 binary outputs
Input and output module
4 current measuring inputs, 4 voltage measuring inputs, 8 binary inputs,
6 binary outputs
Input and output module
8 current measuring inputs, 4 binary inputs, 4 binary outputs
Input and output module
12 binary inputs, 7 binary outputs
Input module
12 temperature inputs
SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-C, Edition 10.2017

Hide quick links: