Siemens SIPROTEC 5 Series Hardware Description page 140

Table of Contents

Advertisement

Plug-In Modules
4.2 Communication Modules
Figure
Connector type
Wavelength
Baud rate
Protocol
Max. line length
Distance 8 km
Laser class 1 as per EN 60825-1/-2
Transmitter power coupled in
multimode optical fiber
Receiver sensitivity
Optical budget
NOTE
i
i
If you use the protection-interface module USART-AG-1LDFO for distances under 4 km, then connect
2 attenuators 7XV5107-0AA00. To continue using the Duplex LC plugs, attach both attenuators at one end
of the remote connection (see the following figure).
[dwdaempf-030211-01.tif, 2, en_US]
Figure 4-7
Distance 60 km
Laser class 1 as per EN 60825-1/-2
Transmitter power coupled in
singlemode optical fiber
Receiver sensitivity
Optical budget
140
1 x duplex LC
λ = 1300 nm
2 Mbit/s for the protection-interface communication
Protection-interface communication
60 km for singlemode optical fibers or
8 km with multimode optical fiber
With the use of 62.5 μm/125 μm and 50 μm/125 μm optical fibers
Minimum
-5.0 dBm
-34.0 dBm
29.0 dB
Optical Remote Connection with Attenuators
With the use of 9 μm/125 μm optical fibers
Minimum
-5.0 dBm
-34.0 dBm
29.0 dB
avg
avg
avg
avg
SIPROTEC 5, Hardware Description, Manual
Maximum
0 dBm
avg
-34.5 dBm
avg
Maximum
0 dBm
avg
-34.5 dBm
avg
C53000-G5040-C002-C, Edition 10.2017