Table 6-4
Pin
1
2
3
4
5
6
7
8
LEDs of the RJ45 Terminals – Integrated Ethernet Interface (Port J)
The light-emitting diodes (LEDs) signal the operating state of the communication link. The operating states are
explained in the following table:
Integrated Ethernet
Interface (RJ45)
LED 1
LED 2
Ethernet COM Link (Port K) (Available only for Modular Devices)
The Ethernet connection to the CB202 PCB assembly (plug-in module assembly with integrated power supply)
is realized using the RJ45 interface.
The RJ45 interface can be used exclusively for the connection of the CB202 module. This terminal is left
unused when no CB202 module is in use.
The light-emitting diodes (LEDs) signal the operating state of the communication connection. The operating
states are explained in the following table:
COM Link (RJ45)
LED 1
LED 2
Table 6-5
Pin
Insulation class
Plug-In Modules
You can find the Technical data for plug-in modules in chapter
SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-C, Edition 10.2017
Connection
Signal
ETH_TX_P
ETH_TX_N
ETH_RX_P
ETH_RX_N
Screen
Signal
ETH_LED1_N
ETH_LED0_N
Signal
CL2_LED0_N
CL3_LED0_N
Connection
Signal
Siemens-specific assignment
SELV (according to IEC 60255-27)
Signal Description
Transmit Data +
Transmit Data -
Receive Data +
Receive Data -
Shield potential
Color
Operating Status
Yellow
Continuously lit: 100 Mbit
Not lit: 10 Mbit
Green
Flashing: Telegram reception
Continuously lit: No communication
Color
Operating State
Yellow
Flashes when a communication module
is inserted in plug-in module position P
Green
Flashes when a communication module
is inserted in plug-in module position N
Signal Description
Connection using a special cable.
Is part of the device delivery.
4 Plug-In
Modules.
Technical Data
6.6 Communication Interfaces