Binary Inputs - Siemens SIPROTEC 5 Series Hardware Description

Table of Contents

Advertisement

6.3

Binary Inputs

Rated voltage range
Current consumption, excited
Power consumption, max.
Pickup time
Dropout time
7
Control voltage for all modules
with binary inputs except the
IO233
Control voltage for binary inputs of
the IO233 modules
Maximum permitted voltage
The binary inputs contain interference suppression capacitors. In order to ensure EMC immunity, use the
terminals shown in the terminal diagrams/connection diagrams to connect the binary inputs to the common
potential.
7
For time-critical applications with low-active signals, consider the specified dropout times. If necessary, provide for active discharge of
the binary input (for example, a resistor in parallel to the binary input or using a change-over contact).
SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-C, Edition 10.2017
DC 24 V to 250 V
The binary inputs of SIPROTEC 5 are bipolar with the exception of the
binary inputs on the IO230, the IO231, and the IO233.
Approx. DC 0.6 mA to 1.8 mA (independent of the control voltage)
0.6 VA
Approx. 3 ms
Capacitive load (supply-line capaci-
tance)
< 5 nF
< 10 nF
< 50 nF
< 220 nF
Adapt the binary-input threshold to be set in the device to the control
voltage.
Range 1 for 24 V, 48 V, and 60 V
Control voltage
Range 2 for 110 V and 125 V
Control voltage
Range 3 for 220 V and 250 V
Control voltage
Range
DC 300 V
Technical Data
6.3 Binary Inputs
Dropout time
< 4 ms
< 6 ms
< 10 ms
< 35 ms
V
≤ DC 10 V
low
V
≥ DC 19 V
high
V
≤ DC 44 V
low
V
≥ DC 88 V
high
V
≤ DC 88 V
low
V
≥ DC 176 V
high
V
≤ DC 85 V
low
V
≥ DC 105 V
high