GE AF-650 GP Design And Installation Manual page 134

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Specifications
Maximum terminal load (AC-1)
Maximum terminal load (AC-15)
Maximum terminal load (DC-1)
Maximum terminal load (DC-13)
Maximum terminal load (AC-1)
Maximum terminal load (AC-15)
Maximum terminal load (DC-1)
Maximum terminal load (DC-13)
Minimum terminal load on 1–3 (NC), 1–2 (NO), 4–6 (NC), 4–5 (NO)
Environment according to EN 60664-1
1) IEC 60947 part 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
2) Overvoltage Category II.
3) UL applications 300 V AC2A.
Cable lengths and cross-sections for control cables
Maximum motor cable length, shielded
Maximum motor cable length, unscreened
Maximum cross-section to control terminals, flexible/rigid wire without cable end sleeves
Maximum cross-section to control terminals, with ferrules without plastic sleeves
Maximum cross-section to control terminals, with ferrules with plastic sleeves
Minimum cross-section to control terminals
1) For power cables, see chapter 12 Terminal and Applicable Wirechapter 13.1 Electrical Data.
Control card performance
Scan interval
Control characteristics
Resolution of output frequency at 0–590 Hz
Repeat accuracy of precise start/stop (terminals 18, 19)
System response time (terminals 18, 19, 27, 29, 32, 33)
Speed control range (open loop)
Speed control range (closed loop)
Speed accuracy (open loop)
Speed accuracy (closed loop), depending on resolution of feedback device
Torque control accuracy (speed feedback)
All control characteristics are based on a 4-pole asynchronous motor.
Environment
Enclosure
Vibration test
Maximum relative humidity
Aggressive environment (IEC 60068-2-43) H
Ambient temperature
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Temperature during storage/transport
Maximum altitude above sea level without derating
Derating for high altitude, see chapter 7.5 Derating.
EMC standards, Emission
EMC standards, Immunity
See section on special conditions in chapter 7.2 Immunity Requirements.
MG35M402
AF-650 GP™ Design and Installation Guide
1)
on 4–5 (NO) (resistive load)
on 4–5 (NO) (inductive load @ cosφ 0.4)
1)
1)
on 4–5 (NO) (resistive load)
1)
on 4–5 (NO) (inductive load)
1)
on 4–6 (NC) (resistive load)
on 4–6 (NC) (inductive load @ cosφ 0.4)
1)
1)
on 4–6 (NC) (resistive load)
1)
on 4–6 (NC) (inductive load)
1)
IP20 Open Chassis, Nema 1 with field installed kit, Nema 12, and Nema 4X
5–93% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
S test
2
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
DET-767c All rights reserved.
2)3)
overvoltage cat. II
Overvoltage category III/pollution degree 2
maximum error ±5% of rated torque
1.0 g (75 kW/100 hp and below)/0.7 g (above 75 kW/100 hp)
EN 61800-3, EN 61000-6-3/4, EN 55011
400 V AC, 2 A
240 V AC, 0.2 A
80 V DC, 2 A
24 V DC, 0.1 A
240 V AC, 2 A
240 V AC, 0.2 A
50 V DC, 2 A
24 V DC, 0.1 A
24 V DC 10 mA, 24 V AC 20 mA
150 m
300 m
2
2.5 mm
/14 AWG
2
2.5 mm
/14 AWG
2
1 mm
/18 AWG
2
0.25 mm
/24 AWG
1 ms
±0.003 Hz
≤±0.1 ms
≤2 ms
1:100 of synchronous speed
1:1000 of synchronous speed
30–4000 RPM: error ±8 RPM
0–6000 RPM: error ±0.15 RPM
class Kd
Maximum 50 °C
0 °C
-10 °C
-25 to +65/70 °C
1000 m
EN 61800-3, EN 61000-6-1/2,
131
13
13

Advertisement

Table of Contents
loading