GE AF-650 GP Design And Installation Manual page 111

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Warnings and Alarms
ALARM 68, Safe Stop activated
Safe Torque Off (STO) has been activated. To resume
normal operation, apply 24 V DC to terminal 37, then send
a reset signal (via bus, digital I/O, or by pressing [Reset]).
ALARM 69, Power card temperature
The temperature sensor on the power card is either too
hot or too cold.
Troubleshooting
Check that the ambient operating temperature is
within limits.
Check for clogged filters.
Check fan operation.
Check the power card.
ALARM 70, Illegal drive configuration
The control card and power card are incompatible. To
check compatibility, contact the GE supplier with the
model number from the unit nameplate and the part
numbers of the cards.
ALARM 71, PTC 1 safe stop
STO has been activated from external source. Normal
operation can be resumed when 24 V DC is applied to
terminal # 37. When that happens, send a reset signal (via
bus or digital I/O, or press [Reset]).
ALARM 72, Dangerous failure
STO with trip lock. An unexpected combination of STO
commands has occurred:
OPCPTC enables X44/10, but STO is not enabled.
0
10
OPCPTC is the only device using STO (specified
through selection [4] PTC 1 Alarm or [5] PTC 1
Warning in parameter E-07 Terminal 37 Safe Stop),
STO is activated, and X44/10 is not activated.
WARNING 73, Safe stop auto restart
STO activated. With automatic restart enabled, the motor
can start when the fault is cleared.
ALARM 74, PTC Thermistor
Alarm related to PTC Thermistor Card OPCPTC. The PTC is
not working.
ALARM 75, Illegal profile sel.
Do not write the parameter value while the motor runs.
Stop the motor before writing the MCO profile to
parameter O-10 Control Word Profile.
WARNING 76, Power Unit Setup
The required number of power units does not match the
detected number of active power units.
Troubleshooting
Confirm that the spare part and its power card
are the correct part number.
WARNING 77, Reduced power mode
The frequency converter is operating in reduced power
mode (less than the allowed number of inverter sections).
This warning is generated on power cycle when the
108
frequency converter is set to run with fewer inverters and
remains on.
ALARM 78, Tracking error
The difference between setpoint value and actual value
exceeds the value in parameter H-25 Tracking Error.
Troubleshooting
Disable the function or select an alarm/warning
in parameter H-24 Tracking Error Function.
Investigate the mechanics around the load and
motor, check feedback connections from motor
encoder to frequency converter.
Select motor feedback function in
parameter H-20 Motor Feedback Loss Function.
Adjust tracking error band in
parameter H-25 Tracking Error and
parameter H-27 Tracking Error Ramping.
ALARM 79, Illegal power section configuration
The scaling card has an incorrect part number or is not
installed. The MK102 connector on the power card could
not be installed.
ALARM 80, Drive initialised to default value
Parameter settings are restored to factory settings after a
manual reset. To clear the alarm, reset the unit.
ALARM 81, CSIV corrupt
CSIV file has syntax errors.
ALARM 82, CSIV parameter error
CSIV failed to initialize a parameter.
ALARM 83, Illegal option combination
The mounted options are incompatible.
ALARM 88, Option detection
A change in the option layout is detected.
Parameter H-01 Option Detection is set to [0] Frozen configu-
ration and the option layout has been changed.
To apply the change, enable option layout
changes in parameter H-01 Option Detection.
Alternatively, restore the correct option configu-
ration.
WARNING 89, Mechanical brake sliding
The hoist brake monitor detects a motor speed exceeding
10 RPM.
ALARM 90, Feedback monitor
Check the connection to encoder/resolver option and, if
necessary, replace OPCENC or OPCRES.
ALARM 91, Analog input 54 wrong settings
Set switch S202 in position OFF (voltage input) when a
KTY sensor is connected to analog input terminal 54.
ALARM 99, Locked rotor
Rotor is blocked.
WARNING/ALARM 101, Speed monitor
The motor speed monitor value is outside range. See
parameter H-30 Motor Speed Monitor Function.
DET-767c All rights reserved.