9.2.4.5 Conversion Factor

The different attributes for each parameter can be seen in
the section on factory settings. Since a parameter value
can only be transferred as a whole number, a conversion
factor must be used to transfer decimals.
Conversion index
67
6
5
4
3
2
1
0
-1
-2
-3
-4
-5
-6
-7
Table 9.13 Conversion Table

9.2.4.6 Parameter Values

9
9
Standard data types
Standard data types are int16, int32, uint8, uint16, and
uint32. They are stored as 4x registers (40001–4FFFF). The
parameters are read using function 03HEX "Read Holding
Registers. " Parameters are written using the function 6HEX
"Preset Single Register" for 1 register (16 bits), and the
function 10 HEX "Preset Multiple Registers" for 2 registers
(32 bits). Readable sizes range from 1 register (16 bits) up
to 10 registers (20 characters).
Non-standard data types
Non-standard data types are text strings and are stored as
4x registers (40001–4FFFF). The parameters are read using
function 03HEX "Read Holding Registers" and written using
function 10HEX "Preset Multiple Registers." Readable sizes
range from 1 register (2 characters) up to 10 registers (20
characters).
92
Conversion factor
1/60 (time)
1000000
100000
10000
1000
100
10
1
0.1
0.01
0.001
0.0001
0.00001
0.000001
0.0000001
DET-767c All rights reserved.

9.3 Drive Control Profile

9.3.1 Control Word According to Drive
Profile (parameter O-10 Control Word
Profile = Drive profile)
Illustration 9.2 Control Word
Bit
Bit value = 0
00
Reference value
01
Reference value
02
DC brake
03
Coasting
04
Quick stop
05
Hold output frequency
06
Ramp stop
07
No function
08
No function
09
Ramp 1
10
Data invalid
11
No function
12
No function
13
Parameter set-up
14
Parameter set-up
15
No function
Table 9.14 Control Word Bits
Explanation of the control bits
Bits 00/01
Bits 00 and 01 are used to select between the 4 reference
values, which are pre-programmed in parameter C-05 Multi-
step Frequency 1 - 8 according to Table 9.15.
Bit value = 1
External selection lsb
External selection msb
Ramp
No coasting
Ramp
Use ramp
Start
Reset
Jog
Ramp 2
Data valid
Relay 01 active
Relay 02 active
Selection lsb
Selection msb
Reverse
MG35M402