Specifications
AF-650 GP
Heavy duty/Ligth duty*
Typical shaft output at 400 V [kW]
Typical shaft output at 460 V [hp]
Typical shaft ouptut at 500 V [kW]
Enclosure IP20
Enclosure IP21, IP54
Output current
Continuous (at 400 V) [A]
Intermittent (60 s overload)
(at 400 V)[A]
Continuous (at 460/500 V) [A]
Intermittent (60 s overload)
(at 460/500 V) [kVA]
Continuous kVA (at 400 V) [kVA]
Continuous kVA (at 460 V) [kVA]
Continuous kVA (at 500 V) [kVA]
Maximum input current
Continuous (at 400 V) [A]
Continuous (at 460/500 V) [A]
Max. cable size: mains, motor, brake
2
1)2)
and load share [mm
(AWG)]
3)
Max. external mains fuses [A]
Estimated power loss at 400 V [W]
Estimated power loss at 460 V [W]
Weight, enclosure IP20, IP21, IP54 [kg/
6)
(lb)]
5)
Efficiency
Output frequency
Heatsink overtemp trip [° C/(° F)]
Control card ambient trip [° C/(° F)]
*High overload=150% current for 60 s, Normal overload=110% current for 60 s
Table 13.7 Technical Specifications, Unit Size 4xh 380–500 V
1) American Wire Gauge.
2) Wiring terminals on N132, N160, and N315 frequency converters cannot receive cables one size larger.
3) For fuse ratings, see chapter 13.3 Fuse Specifications.
4) Typical power loss is at normal conditions and expected to be within
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the frequency converter.
Applies for dimensioning of frequency converter cooling. If the switching frequency is higher than the default setting, the power losses may
increase. Keypad and typical control card power consumptions are included. Options and customer load can add up to 30 W to the losses, though
usually a fully loaded control card and options for slots A and B each add only 4 W.
5) Measured using 5 m (16.4 ft) screened motor cables at rated load and rated frequency.
Efficiency measured at nominal current. For energy efficiency class, see chapter 13.2 General Technical DataEnvironment.
6) Additional frame size weights are as follows: 45h - 166 (255) / 46h - 129 (285) / 47h - 200 (440) / 48h - 225 (496). Weights are in kg (lbs).
MG35M402
AF-650 GP™ Design and Installation Guide
125 hp
150 hp
HD
LD
HD
90
110
110
125
150
150
110
132
132
43h
43h
41h
41h
177
212
212
266
233
318
160
190
190
240
209
285
123
147
147
127
151
151
139
165
165
171
204
204
154
183
183
2x95 (2x3/0)
315
350
4) 5)
2031
2559
2289
2954
4) 5)
1828
2261
2051
2724
62 (135)
75 (167)
DET-767c All rights reserved.
175 hp
250 hp
LD
HD
LD
HD
132
132
160
160
200
200
250
250
160
160
200
200
43h
44h
41h
42h
260
260
315
315
286
390
347
473
240
240
302
302
264
360
332
453
180
180
218
218
191
191
241
241
208
208
262
262
251
251
304
304
231
231
291
291
400
550
2923
3770
3093
4116
2089
3628
2872
3569
0.98
0-590 Hz
110 (230)
±
15% (tolerance relates to variety in voltage and cable conditions.) These
300 hp
350 hp
LD
HD
LD
HD
200
200
250
250
300
300
350
350
250
250
315
315
44h
44h
42h
42h
395
395
480
480
435
593
528
720
361
361
443
443
397
542
487
665
274
274
333
333
288
288
353
353
313
313
384
384
381
381
463
463
348
348
427
427
2x185 (2x350 mcm)
630
800
4039
5137
5005
6674
3575
4566
4458
5714
125 (275)
80 (176)
LD
315
450
355
588
647
535
588
407
426
463
567
516
13
13
119