• dL P (Download Partial) – Copies a partial parameter set from the Control Panel
to a drive. The partial set does not include internal motor parameters, parameters
9905...9909, 1605, 1607, 5201, nor any Group 51 and Group 53 parameters. Use
this option to transfer parameters to systems that use similar configurations – the
drive and motor sizes do not need to be the same.
• dL u1 (Download User Set 1) – Copies
using parameter 9902
• dl u2 (Download User Set 2) – Copies
Panel to the drive.
1. Starting from the Output mode, press MENU/ENTER.
The display shows one of the following alternate modes:
• reF (Reference)
• PAr (Parameter)
• CoPY (Copy)
2. Use UP or DOWN arrow key to step through to the "CoPY" (Copy) Mode.
3. Press MENU/ENTER.
The display shows one of the following copy options:
• uL (Upload)
• rE A (Restore All)
• dL P (Download Partial)
4. Use UP or DOWN arrow key to step to the desired option.
5. Press MENU/ENTER.
The parameter set is transferred as directed. During the transfer, the display shows
the transfer status as a percent of completion.
6. Press EXIT/RESET to step back to the Output mode.
Handling Inexact Downloads
In some situations, an exact copy of the download is not appropriate for the target
drive. The Basic control panel automatically handles these situations by:
• Discarding parameters/values not available on the target drive.
• Using parameter default values when the download provides no values or invalid
values.

Alarm Codes

The Basic Control Panel indicates Control Panel alarms with a code of the form
A5xxx. See "Alarm Codes (Basic Control Panel)" on page 209 for a list of the alarm
codes and descriptions.