3.4.2 Set XYR 400E to same network as PC

This is the alternate procedure to setting an IP address in the XYR 400E. Consult your network
administrator for an IP address on your network, the gateway IP address, and network mask.
a) Switch Factory Default dip-switch on XYR 400E to SETUP position.
b) Connect the RS232 port on the XYR 400E to the RS232 port on the PC using a "straight-
through" serial cable.
c) Open a terminal package (such as Hyperterminal) with 19200bps data rate, 8 data bit, 1 stop, no
parity and no flow control. Make sure that no other programs have control of the serial port.
d) Power up XYR 400E. Basic network settings will be displayed on the terminal as illustrated
below. When prompted, hit enter key to stop automatic boot process. You have 5 seconds to
abort the boot process.