Wireless ethernet modem
Table of Contents

Advertisement

Set dipswitch to RUN
Save the changes and unit will restart with new settings.
Alternate procedure – Adjust XYR 400E network settings using serial port(assuming
configuration PC is on existing network)
a) Open terminal program with settings with data rate 19200bps, 8 data bits, 1 stop bit
and no parity.
b) Set dipswitch to SETUP
c) Connect straight through serial cable to XYR 400E and power up unit.
d) When prompted, strike the Enter key to abort automatic boot
e) Set IP address of XYR 400E to 192.168.0.200 with command bip 192.168.0.200
f)
Set netmask of XYR 400E to 192.168.0.200 with command bnm 255.255.255.0
g) Set gateway address of XYR 400E to 192.168.0.1 with command bgw 192.168.0.1
h) Set dipswitch to RUN
i)
Reset XYR 400E with reset command.
j)
Open configuration webpage with Internet Explorer at address http://192.168.0.200/
When prompted for password, enter default username "user" and password "user"
Enter "Network", and select Operating Mode as Access Point.
Select Device Mode as Bridge.
Change the IP address to 192.168.0.200
Enter a System Address (SSID) string
Select the Radio Encryption required, and enter the system keys. Make a record of
these Encryption keys and use these on all modules in the system.
Set dipswitch to RUN
Save the changes and unit will restart with new settings.
Client 1 Configuration
Perform the same configuration steps as the Access Point configuration with the following
differences:
• set the Ethernet and Wireless IP addresses of XYR 400E to 192.168.0.201
• set the Operating Mode to Client.
Ensure the same System Generator String is used and the same Radio Encryption method is
selected.
Client 2 Configuration
• As above, however set the Ethernet and Wireless IP addresses as 192.168.0.202
Version 1