Download Print this page

Honeywell Multi-Mon Installation Instructions Manual page 57

Multiple circuit energy monitor

Advertisement

APPENDIX E:
DATA SCALES
The maximum values for volts, amps and power in the Multi-Mon setup and in communications are limited by the voltage and
current scale settings. See Basic Meter Setup in Section 4 on how to change the voltage scale in your meter.
The following table defines the meter data scales.
Scale
Maximum voltage (V max)
Maximum current (I max)
1
Maximum power
1
Maximum power is rounded to whole kilowatts. With PT=1.0, it is limited to 9,999,000 W.
Range
Voltage scale × PT Ratio, V The default voltage scale is 600V
CT Primary current × 2, A
V max × I max × 2, W
Notes
The default CT primary current is 50A