Multiple circuit energy monitor

Advertisement

MULTI-MON
The following table lists available device configuration options.
Parameter
PT Ratio
Primary current
Nominal frequency
Block power demand period 1, 2, 5, 10, 15, 20, 30, 60 min
The number of blocks in the
sliding window
Volt demand period
Ampere demand period
Power calculation mode
Energy roll value, kWh
31-00035—01
Options
Basic Configuration
1.0-6500.0
1-10000 A
50, 60 Hz
1-15
0-9000 sec
0-9000 sec
Device Options
S=f(P, Q)
(using reactive power),
Q=f(S, P)
(using non-active power)
100000.0 kWh
1000000.0 kWh
10000000.0 kWh
100000000.0 kWh
Fig. 27.
Default
The phase potential transformer's primary to secondary ratio
1.0
The CT primary current of the submeter's; for information only.
50 A
The nominal power frequency
60 Hz
Demand Setup
The length of the demand period for power demand
30
calculations
The number of block demand periods to be averaged for
1
sliding window demands
The length of the demand period for volt demand calculations
900 sec
The length of the demand period for ampere demand
900 sec
calculations
The method used for calculating reactive and apparent
S=f(P, Q)
powers (see "Power Calculation Modes" below)
100000000.0 The value at which energy counters roll over to zero
30
Description