Zone Outputs; Mapping To Zone Events - Honeywell Silent Knight IntelliKnight 5820XL Installation And Operation Manual

Addressable fire system
Table of Contents

Advertisement

7.3.1.3 Zone Outputs

Output groups and cadence patterns are mapped to events. They can be programmed to output
when an event occurs in a zone. Some system trouble events can be mapped for the entire
system. Section 6.2 of this manual contains a general explanation of mapping. The following
sections explain how to select mapping options.
Note: Use of multiple notification groups may not synchronize with each other.

Mapping to Zone Events

Eight types of events can occur in zones. For each event type, you can activate up to 8 output
groups or output group template, specifying a pattern for each. The following is a list of all
event types:
Note: Abbreviations in the parenthesizes are the characters that are displayed in programming (see
Figure 7-3).
Manual Pull Alarm (MP)
Water Flow Alarm (WF)
Detector Alarm (DE). This applies to heat or smoke detectors.
Aux 1 and Aux 2 Alarm (A1 or A2). User-specified alarm types.
Pre-alarm (PR)
Supervisory (SU)
Trouble (TR)
To map zone events to outputs:
1. From the Installer Main Menu, select
2. From the Program Menu, select
3. From the next menu, select
4. Enter the zone number you wish to edit.
5. From the next menu, select
6. From the next screen, a list of 8 event types will display. Select the event type you want to
program. A screen similar to the one shown in Figure 7-3 will display. Press
7. Press the
or
template depending on want you need for this zone. Press
151209
for Program Menu.
7
for Zone.
2
for Edit Zone.
1
for Zone Outputs.
3
key to toggle the group letter to either G = Group or T = output group
firealarmresources.com
Programming
.
.
7-7