Working With A Printer - Honeywell Silent Knight IntelliKnight 5820XL Installation And Operation Manual

Addressable fire system
Table of Contents

Advertisement

IntelliKnight 5820XL Installation Manual

8.5.17 Working with a Printer

If you are using the Model 5824 serial/parallel interface module, several printing options are
available. See Section 4.7 for information about installing the 5824.
1. From the Main Menu, select
2. From the next screen, select the 5824 module where the printer is connected.
3. If the printer is not currently busy printing another report, a screen with the following
options will be available. If the printer is busy, a message will display. You can press
cancel the current print job. These options will then display.
Enables event logging, which causes the printer to continuously print events as they occur. The
1
= Event Logging
date/time will print in 24-hour military format. Once event logging is enabled, it will remain
enabled until canceled by the installer. If you need to disable event logging, return to this option
and press
Sample Event Log
Prints the up-to-1000 events currently stored in the panel's event history buffer. Events print
2
= Print Event History
starting with the newest. The date and time printed will be when the event actually occurred and
will print in 24-hour military format.
Sample Event
History Print-Out
Prints the current status of all detectors in the system. This is a method for finding out if any
3
= Print Detector
detectors are out of NFPA compliance or any detectors need maintenance (are approaching an
Status
out of compliance condition).
Sample Detector
Status Print-Out
Note: Detector status can also be viewed and printed using the 5660 SKSS or 5670 SKSS (facility monitoring
only).
8-10
Printer Options.
5
1
to disable.
EVENT LOG:
02/17/97 11:23 Event: System Silenced
02/17/97 11:24 Event: System Reset
02/17/97 14:30 Event: Local Programming Begin
02/17/97 15:01 Event: Local Programming Ended Successfully
EVENT LOG:
EVENT HISTORY:
02/20/97
09:02
Event
3 of 10: System Silenced
02/20/97
09:05
Event
2 of 10: System Reset
02/22/97
08:47
Event
4 of 10: Printer Off Line 4
02/22/97
08:52
Event
4 of 10: Printer On Line 4
02/25/97
15:54
Event
5 of 10: Local Programming Begin
02/25/97
16:10
Event
5 of 10: Local Programming Ended Successfully
02/28/97
12:50
Event
6 of 10: Walk Test Begin
02/28/97
13:31
Event
2 of 10: Walk Test End
. .
.
firealarmresources.com
STARTED: 02/17/97 02:23
STOPPED: 02/17/97 15:02
PRINTED:
02/28/97
13:35
to
1
151209