Current Draw Worksheet - Honeywell Silent Knight IntelliKnight 5820XL Installation And Operation Manual

Addressable fire system
Table of Contents

Advertisement

3.6.2

Current Draw Worksheet

Use Table 3-1 to determine current requirements during alarm/battery standby operation You
can install up 99 devices per loop (1016 max per panel). Copy this section if additional space
is required.
Device
For each device use this formula:
IntelliKnight 5820XL Fire Panel
(Current draw from battery)
Addressable SLC Devices
SD500-AIM
SD500-MIM
SD500-PS
SD500-ARM
SD505-AHS
SD505-AIS
SD505-APS
SD500-ANM
SD500-SDM
SD500-LED
SLC Accessory Bases
SD505-6RB
SD505-6SB
SD505-ADHR
SD505-DTS
SD505-ADH
SLC Isolator Devices
SD505-LIM
SD505-6IB
Accessories Modules
5815XL SLC Expander
151209
Table 3-1: Current Draw Worksheet
# of Devices
Current per Device
This column
X
This column
Standby:
1
Alarm:
1
Standby/Alarm:
(508 max.)
Aux. Pwr
1
(508 max.)
SLC
SLC
1
(508 max.)
Aux. Pwr
Aux. Pwr
1
(100 max.)
SLC
(508 max.)
Standby/Alram:
Aux. Pwr
(508 max.)
SLC
Aux. Pwr
(508 max.)
SLC
(508 max.)
(508 max.)
(1024 max.)
Standby/Alarm
(508 max.)
(3 max.)
Standby/Alarm:
firealarmresources.com
Before You Begin Installing
Standby
Current
=
Current per number of devices.
215 mA
215 mA
385 mA
0.55 mA
Standby:
8 mA
Alarm:
60 mA
Standby/
Alarm:
.55 mA
Standby/
Alarm:
.55 mA
Standby:
20 mA
Alarm:
106 mA
Standby:
10 mA
Alarm:
220 mA
LED:
10 mA
Standby/
Alarm:
0.55 mA
.082 mA
Standby:
1 mA
Alarm:
32 mA
Standby/
Alarm:
.082 mA
2
Standby:
35 mA
2
Alarm:
75 mA
Standby/
Alarm:
.082 mA
None, included with SD505-ADHR worst case.
None, included with detector current.
0.092 mA
55 mA
Alarm
Current
385 mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
3-7