3) When necessary, activation of Notification Appliances can be prevented by the DISABLE
function
Testing:
1) Activate a input via an alarm initiating device and check that the correct outputs activate
(Notification Appliances sound/flash, relays activate, alarm LED lights). Reset system.
Repeat for each alarm initiating device.
2) Momentarily open the following circuits one at a time and check for a trouble signal:
Notification Appliance (bell) Circuits.
Initiating devices
3) If new batteries were installed, wait 48 hours before completing this step. Remove AC
power, activate initiating device and check that :
The ALARM indicator lights.
All active Notification Appliances sound.
Measure battery voltage while the Notification Appliances are sounding. Replace any battery
with terminal voltage less than 85% of rating. Reapply AC power and RESET system.

10.2.2 Event History

The event history can be useful for tracking or recalling a trouble condition.