8. Select options for each event that could occur in this zone. Figure 7-3 is a complete exam-
ple of how you might map a zone.
Indicates output group 1, cadence
pattern 00 has been selected. 00 is
a constant output cadence.
Indicates type of event (in
this case, Manual Pull alarm).
See Section 6.5 for choices.
Figure 7-3 Selecting Output Groups/templates and Cadence Patterns for a Zone Event

Zone Mapping Example

Suppose you want to program Zone 1 so that:
Any alarm (detector, water flow or manual pull) would activate Output Group 1 using the
ANSI cadence pattern.
Manual pull alarm would activate Output Group 3 using constant output.
Troubles would activate Output Group 2 using the zone-coded cadence pattern.
To accomplish this you need to access the screen for each event and then select your output
7-8
"T" Indicates output group
template 1. See Section 7.4.5 for
more information on output group
templates.