4.15 Remote Station Applications

4.15.1 Keltron Model 3158 Installation

The control panel is compatible with Keltron Model 3158, used for direct connection to a
Keltron receiver. The 3158 reports alarms, supervisories, and troubles.
The steps for connecting the 3158 to the control panel. Refer to the 3158 installation
instructions for complete information.
1. Wire the 3158 to the control panel as shown in the connection list and Figure 4-40.
2. Wire the 3158 within 20 feet of the control panel. Wiring must be enclosed in conduit.
3. Program control panel Relay 1 for alarm.
4. Program Flexput circuit 5 for alarm.
5. Program Flexput circuit 6 for supervisory non latching.
Table 4-3: Keltron 3158 to Control Panel Connections
Terminal #
3158 Term. 1
To Keltron receiving equipment
3158 Term. 2
To Keltron receiving equipment
3158 Term. 3
Earth ground
3158 Term. 4
Not used; no connection.
3158 Term. 5
Control panel Term. 18
3158 Term. 6
Control panel Term. 19
3158 Term. 7
Control panel Term. 7
Not suitable for remote station
protected premise service
where separate transmission
circuits are required for fire
supervisory (if applicable), and
trouble signals.
Intended for connection to a
polarity reversal circuit of a
remote station receiving unit
having compatible ratings.
Figure 4-40 Keltron 3158 Connection to Control Panel
151209
Connects To
3158 Term. 8
3158 Term. 9
3158 Term. 10
Control panel Term. 6
Control panel Term. 28 Control panel Term. 31
Control panel Term. 29 Control panel Term. 30
firealarmresources.com
Control Panel Installation
Terminal #
Connects To
Control panel Term. 28
Control panel Term. 5
Control panel Term. 4
Control panel Term. 29
Example
4-41