60 Appendix B - Module configuration backup
Configuration
Ethernet service configuration
Web page password
SNTP configuration
The settings are saved to the drive after 10 seconds. If a Refresh command is given
to FBIP-21 using parameter 51.27, the pending backup is transferred to drive
immediately and FBIP-21 is rebooted after the transfer is completed.
Note: The new setting is not saved to drive if the drive was powered off or the adapter
was disconnected from the drive within 10 seconds of changing a setting.

Using the restored backup

The use cases in the below table show how FBIP-21 settings are used after you restored
a backup or after you powered up or enabled the module. The matching status box
colours indicate matching configurations.
No.
Configuration status
Before restore
1
Restoring a backup to drive with Drive composer or panel.
Drive and fieldbus adapter can have any con-
figuration.
2
Replacing a new fieldbus adapter of the same type.
Drive has a backup of FBIP-21 configuration
and a new FBIP-21 with no configuration is in-
stalled.
Description
Enables different Ethernet services. See
page (page
66).
When set, backup will automatically include this configuration.
Login password for accessing FBIP-21 configuration web pages. See
Password
page.
Backup will automatically include the set password.
Note: Backup will include the default password.
Enables SNTP, request interval, UTC offset, and server addresses. See
Service configuration page (page
When set, backup will automatically include this configuration.
Service configuration
66).
After restore
Configuration from backup is used in drive
and in FBIP-21
Drive backup is used in FBIP-21.