Electrical installation

Contents of this chapter

This chapter contains general cabling instructions and instructions on connecting the
FBIP-21 adapter module to the BACnet/IP network.

Necessary tools and instructions

See the drive hardware manual.

General cabling instructions

Arrange the bus cables as far away from the motor cables as possible.
Avoid parallel runs.
Use grommets at cable entries.

Connecting the FBIP-21 to the BACnet/IP network

WARNING!
Obey the safety instructions of the drive. If you ignore them, injury or
death, or damage to the equipment can occur.
Choose correct cable for your application, CAT5e and CAT6 cables are recommended.
ABB recommends to use double shielded twisted pair cables, eg. "SF/FTP".
Electrical installation 21