Frequency Reference; Speed Reference; Miscellaneous Drive Control - ABB FBIP-21 BACnet/IP User Manual

Adapter module
Table of Contents

Advertisement

30 Start-up

Frequency reference

For using the BACnet/IP to provide input frequency references to the drive, configure
the following drive parameters and set the fieldbus controller supplied reference
word(s) in the appropriate location:
Drive parameter
19.11 Ext1/Ext2 selection
28.11 Ext1 frequency ref1
28.15 Ext2 frequency ref1
46.02 Frequency scaling
50.04 FBA A ref1
type/50.05 FBA A ref2
type
1) As example

Speed reference

For using the BACnet/IP to provide input speed references to the drive, configure the
following drive parameters and set the fieldbus controller supplied reference word(s)
in the appropriate location:
Drive parameter
19.11 Ext1/Ext2 selection
22.11 Ext1 speed ref1
22.18 Ext2 speed ref1
46.01 Speed scaling
50.04 FBA A ref1
type/50.05 FBA A ref2
type

Miscellaneous drive control

To use the BACnet/IP for different drive control functions, configure the following
drive parameters and set the fieldbus controller supplied command(s) in the
appropriate location:
Value
Description
2 = FBA A MCW bit
Reference set selection
by fieldbus
1)
Frequency reference
3 = FBA ref1
source 1
1)
5 = FBA ref2
Frequency reference
source 2
1)
50.00 Hz
16-bit scaling of fre-
quency-related paramet-
ers
0 = Speed or frequency
References (1 or 2) type
for scaling defined in
5 = Frequency
parameter 46.02 Fre-
quency scaling
Value
Description
2 = FBA A MCW bit
Reference set selection
by fieldbus
1)
3 = FBA ref1
Speed reference source
1
1)
5 = FBA ref2
Speed reference source
2
1)
1500 rpm
16-bit scaling of speed-
related parameters
0 = Speed or frequency
References (1 or 2) type
for scaling defined in
4 = Speed
parameter 46.02 Fre-
quency scaling
BACnet access point
BV13
AV16
AV17
AV16/AV17
AV16/AV17
BACnet access point
BV13
AV16
AV17
AV16/AV17
AV16/AV17

Advertisement