ABB FBIP-21 BACnet/IP User Manual page 52

Adapter module
Table of Contents

Advertisement

52 Diagnostics
Name
Color
HOST
Blinking green
Green
Blinking red
Flashing orange, al-
ternating with the
MODULE flashing
orange
MODULE
Off
Flashing orange
Orange
Flashing green
Green
Flashing red
Red
Flashing orange, al-
ternating with the
HOST flashing or-
ange
Flashing red/green
NETWORK /
Off
NET
Flashing green
Flashing orange
Function
Establishing communication to host
Connection to host OK
Communication to host lost temporarily
Internal file system error. The error may be cleared by cycling drive
power. If the error persists, contact your local ABB representative.
There is no power applied to the device.
Device is attempting to obtain IP configuration from the DHCP
server.
Device is executing Duplicate Address Detection.
Device is waiting for a BACnet request.
Device has received a BACnet request within the timeout period.
Ethernet link is down.
• Ethernet interface is disabled.
• Duplicate Address Detection may have detected a duplicate
address. Check the IP configuration and either initiate a Fieldbus
Adapter parameter refresh or cycle power to the drive.
or
• Drive is not supported by FBIP-21.
Internal file system error. The error may be cleared by cycling drive
power. If the error persists, contact your local ABB representative.
Device is in boot mode, ready for firmware update (HOST led is
Off).
BACnet link is down.
BACnet link is up at 100 Mbps.
Flashing indicates activity on interface.
BACnet link is up at 10 Mbps. Flashing indicates activity on interface.