36 Start-up
Starting up BACnet/IP communication for ACH480 and
ACH580 drives
Follow these steps to setup fieldbus communication in ACH480 or ACH580 drives.
For example of appropriate values, see
1.
Power up the drive.
2.
Enable communication between the adapter module and the drive with parameter
50.01 FBA A enable.
3.
Configure network settings with parameters 51.03...51.13.
4.
Define the device object instance value with parameters 51.14 Device obj ID lo
and 51.15 Device obj ID hi.
Note: The object instance value should be unique and in the range 1...4194303.
5.
Configure the BACnet UPD port number with parameter 51.18 BACnet/IP Port if
necessary.
6.
Define communication loss function to monitor the communication between
fieldbus master and adapter module and between adapter module and drive:
With parameters 51.20 and 51.21, set the timeout time and timeout mode.
With parameter 50.03 FBA A comm loss t out, define the communication
break reaction time.
With parameter 50.02 FBA A comm loss func, select how the drive reacts to
a fieldbus communication break.
7.
With parameter 96.07 Parameter save manually, save the valid parameter values
to permanent memory.
8.
With parameter 51.27 FBA A par refresh, validate the settings made in parameter
group 51.
9.
Set the relevant drive control parameters to control the drive according to the
application.

Parameter setting examples

Frequency control

This table shows a parameter setting example for a frequency control application.
The rest of parameters are in default values.
Drive parameter
50.01 FBA A enable
51.01 FBA A type
51.03 Commrate
51.04 IP configuration
Parameter setting examples (page
Settings
1 = Enable
1)
47808 = BACnet
2)
0 = Auto
1 = Static IP
36).
Description
Enables communication between
the drive and fieldbus adapter A,
and specifies the slot the adapter
is installed into.
Shows the fieldbus adapter type
as detected by the drive.
BACnet communication rate is
negotiated automatically by the
device.
Configuration is obtained
through parameter 51.05...51.13.