ABB FBIP-21 BACnet/IP User Manual page 46

Adapter module
Table of Contents

Advertisement

46 Communication protocol
Object
Default object name
ID
BV19
Control- Override-
Monitor
BV20
Start- Interlock-1-
Command
BV21
Start- Interlock-2-
Command
BV24
Started- Monitor
BV25
Safe-Torque-Off-Mon-
itor
BV26
Underload-Monitor
BV27
Overload-Monitor
BV28
Motor-Heating-Com-
mand
BV29
Motor-Heating-Monit-
or
BV30
User0- Monitor
BV31
User1- Monitor
BV32
User2- Monitor
BV33
User3- Monitor
BV34
User0- Command
BV35
User1- Command
BV36
User2- Command
BV37
User3- Command
BV39
Parameter- Save-
Command
BV40
PID-Set-Select
Description
Indicates if drive is
placed in BACnet Con-
trol Override by com-
manding BV18. In this
mode BACnet ac-
quires drive control
from its normal
source. Note that
HAND mode of the
panel has priority over
BACnet Control Over-
ride.
Command to start in-
terlock 1
Command to start in-
terlock 2
Actual start status
Actual status of Safe
Torque Off
Underload status
Overload status
Command to motor
heating mode
Actual status of motor
heating mode
User 0 status
User 1 status
User 2 status
User 3 status
User 0 command
User 1 command
User 2 command
User 3 command
Parameter save com-
mand
Command to Process
PID set1 or Process
PID set2 selection
Default active/ Inact-
ive text
ON / OFF
ENABLE / DISABLE
ENABLE / DISABLE
STARTED / NOT-
STARTED
Active / OK
UNDERLOAD / OK
OVERLOAD / OK
ON / OFF
ON / OFF
ON / OFF
ON / OFF
ON / OFF
ON / OFF
ON / OFF
ON / OFF
ON / OFF
ON / OFF
SAVE / NO
Set1 / Set2
Present value access
type
R
C
C
R
R
R
R
W
R
R
R
R
R
C
C
C
C
W
W

Advertisement