Object
Default object name
ID
AV18
Active-Fault
AV19
Previous-Fault-1
AV20
Previous-Fault-2
AV21
AO1-Monitor
AV22
AO2-Monitor
AV23
Accel-1-Seconds
AV24
Decel-1-Seconds
AV25
Mbox-Param
AV26
Mbox-Data
AV29
Min-Speed
AV30
Max-Speed
AV31
Output-Speed
AV32
Output-Current-
Range
AV33
Max-Current
AV34
DC-Ripple
AV40
LOOP-Feedback-
Monitor
AV41
LOOP-Setpoint-Monit-
or
AV42
LOOP-Setpoint
AV43
LOOP-Feedback
AV44
LOOP-Output
AV45
LOOP-Gain
AV46
LOOP-Integration-
Time
AV49
LOOP-Deviation-
Monitor
AV53
LOOP-1-Gain
Description
Active fault
Previous fault- 1
Previous fault- 2
Output level of Analog Output
1
Output level of Analog Output
2
For frequency reference chain
For frequency reference chain
Parameter number to be used
by mailbox function.
Set (W) or indicate (R) of the
data value of mailbox function
Minimum speed
Maximum speed
Actual motor speed
Actual motor current
Max motor current
DC bus ripple voltage
Loop controller feedback
Loop setpoint monitor
Loop setpoint
Loop feedback
Loop output
Loop gain
Loop integration time
Loop controller deviation
Loop-1 gain
Minimum/ Maxim-
Unit
um present value
(information, de-
pends on the drive
parameter)
-
No
unit
-
No
unit
-
No
unit
0, 100
%
0, 100
%
0, 1800
s
0, 1800
s
-
No
unit
-
No
unit
-500, 500
Hz
-500, 500
Hz
-200, 200
%
0, 200
%
0, nominal current
A
0, 200
V
0, 100
%
0, 100
%
0, 100
%
0, 100
%
0, 100
%
0.1, 100
No
unit
0, 3600
s
0, 100
%
0.1, 100
No
unit
Present
value ac-
cess type
R
R
R
R
R
W
W
W
W
W
W
R
R
W
R
R
R
C
W
R
W
W
W

Advertisement