28 Start-up
No.
Name/Value
Description
0...65535
Drive type code of the fieldbus adapter module mapping file
30
FBA Mapping
Displays the fieldbus adapter module mapping file revision stored
file ver
in the memory of the drive in decimal format.
This parameter is read-only.
0...65535
Mapping file revision
31
D2FBA comm
Displays the status of the fieldbus adapter module communication.
status
This parameter is read-only.
Note: The value names may vary by drive.
0 = Idle
Adapter is not configured.
1 = Exec.init
Adapter is initializing.
2 = Time out
A timeout has occurred in the communication between the adapter
and the drive.
3 = Conf.err
Adapter configuration error
4 = Off-line
Adapter is off-line.
5 = On-line
Adapter is on-line.
6 = Reset
Adapter is performing a hardware reset.
32
FBA comm SW
Read-only. Displays the firmware patch and build number of the ad-
ver
apter module in format xxyy, where:
xx = patch number
yy = build number.
Example: C80D ≥ 200.13 or 0 ≥ 0.0
0..0xFFFF
Firmware patch and build number of the adapter module
33
FBA appl SW ver
Read-only. Displays the firmware version of the adapter module in
format xxyy, where:
xx = major revision number
yy = minor revision number.
Example: 0041h = 0.41
Version number is in the form:
<major>,<minor>,<patch>,<build>
Example: 0.41.200.6 or 0.41.0.0
0..0xFFFF
Firmware version of the adapter module
Default
0
0 = Idle
0 hex
0 hex